Find generator sizes: 7 kW 10 kW 13 kW 20 kW up to 150 kW Single and Three Phase Commercial Generators
| Revolutionizing
the Commercial and Home Standby Power Generator Market GUARDIAN® has long been known as America’s #1 choice in home standby generators. Now, we’re fast becoming recognized as the company that revolutionized the commercial market. That’s because we’ve eliminated the noise, fuel and installation concerns that traditionally made commercial standby power too costly. GUARDIAN Elite™ generators are reliable and value-oriented. So much so, they often pay for themselves during the first extended outage. Single and Three Phase available in selected Generators. See below for information.
|
![]() |
|
|
|
| Model Number | QT02016 | QT02516 | QT03524 | QT04524 |
| Rated Power LP (kW) | 20 | 25 | 35 | 45 |
| Rated Power NG (kW) | 20 | 25 | 35 | 43 |
| Amps @ 208V, 3Ø | 70 | n/a | 122 | 156 |
| Amps @ 480V, 3Ø | n/a | n/a | 53 | 68 |
| Voltage @ 60 Hz | 120/208 | 120/208 | 120/208, 277/480 | 120/208, 277/480 |
| Phase | Three | Three | Three | Three |
| Frequency | 60 Hz | 60 Hz | 60 Hz | 60 Hz |
| Engine/Alternator RPM | 3600/3600 | 3600/3600 | 3600/3600 | 3600/3600 |
| Engine | 1.6L OHC 4 cyl. | 1.6L OHC 4 cyl. | 2.4L OHC 4 cyl. | 2.4L OHC 4 cyl. |
| Fuel Consumption LP (cu.ft./hr.)/(gal./hr.) |
125 (3.44) | 175 (4.81) | 222.3 (6.1) | 286 (7.86) |
| Fuel Consumption NG (cu.ft./hr.) | 315 | 437 | 560 | 720 |
| EPA/CARB Certified | Yes | Yes | Yes | Yes |
| Fuel | Natural Gas LP Vapor |
Natural Gas LP Vapor |
Natural Gas LP Vapor |
Natural Gas LP Vapor |
| Engine Cooling | Liquid | Liquid | Liquid | Liquid |
| Controls | R-Series | R-Series | R-Series | R-Series |
| UL 2200 (US and Canada) | Yes | Yes | Yes | Yes |
| Sound Output dB(A) at 23 ft. with generator operating at full load | 72 | 73 | 71 | 72 |
| Sound Output dB(A) at 23 ft. with generator in WhisperTest™ low speed exercise mode | 62 | 63 | 57 | 58 |
| Main Line Circuit Breaker | 80 Amp | 100 Amp | 150, 60 Amp | 175, 80 Amp |
| Aluminum Enclosure Option | Yes | Yes | Yes | Yes |
| Dimensions (L" x W" x H") | 71 x 29.5 x 36 | 71 x 29.5 x 36 | 77 x 33.5 x 45 | 77 x 33.5 x 45 |
| Unit Wt. (lbs.) (steel/aluminum) | 784/694 | 794/704 | 1393/1276 | 1414/1297 |
Generator Set
|
| Model # | QT06030 | QT07068 | QT08046 |
| Rated Power LP (kW) | 60 | 70 | 80 |
| Rated Power NG (kW) | 60 | 70 | 80 |
| Amps @ 240V, 1Ø | 250 | 292 | 333 |
| Amps @ 208V, 3Ø | 208 | 243 | 278 |
| Amps @ 480V, 3Ø | 90 | 105 | 120 |
| Voltage @ 60 Hz | 120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
| Phase | Single and 3-Phase | Single and 3-Phase | Single and 3-Phase |
| Frequency | 60 Hz | 60 Hz | 60 Hz |
| Engine/Alternator RPM | 3600/3600 | 1800/1800 | 3600/3600 |
| Engine | 3.0 V-6 | 6.8L V-10 | 4.6L V-8 |
| Fuel Consumption LP (cu.ft./hr.)/(gal./hr.) |
376.3 (10.34) | 411 (11.3) | 465 (12.78) |
| Fuel Consumption NG (cu.ft./hr.) | 960 | 1020 | 1154 |
| EPA/CARB Certified | Yes | Yes | Yes |
| Fuel | Natural Gas LP Vapor |
Natural Gas LP Vapor |
Natural Gas LP Vapor |
| Engine Cooling | Liquid | Liquid | Liquid |
| Controls | R-100 | H-100 | H-100 |
| UL 2200 (US and Canada) | Yes | Yes | Yes |
| Sound Output dB(A) at 23 ft. with generator operating at full load | 73 | 71 | 74 |
| Sound Output dB(A) at 23 ft. with generator in WhisperTest™ low speed exercise mode | 62 | 60 | 61 |
| Main Line Circuit Breaker | 300, 250, 100 Amp | 300, 250, 125 Amp | 350, 300, 150 Amp |
| Aluminum Enclosure Option | Yes | Yes | Yes |
| Dimensions (L" x W" x H") | 88.6 x 33.5 x 47.8* | 96.5 x 36.8 x 47.9 | 115.2 x 36.8 x 54.8* |
| Unit Wt. (lbs.) (steel/aluminum) | 1650/1513 | 2185/2040 | 2010/1836 |
* Does not include measurement of exhaust stack(s)
Generator Set
|
| Model # | QT10054 | QT10068 | QT13068 | QT15068 |
| Rated Power LP (kW) | 100 | 100 | 130 | 150 |
| Rated Power NG (kW) | 100 | 100 | 130 | 150 |
| Amps @ 240V, 1Ø | 417 | 417 | 542 | 625 |
| Amps @ 208V, 3Ø | 347 | 347 | 451 | 520 |
| Amps @ 480V, 3Ø | 150 | 150 | 195 | 226 |
| Voltage @ 60 Hz | 120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
120/240, 1Ø 120/208, 3Ø 277/480, 3Ø |
| Phase | Single and 3-Phase |
Single and 3-Phase |
Single and 3-Phase |
Single and 3-Phase |
| Frequency | 60 Hz | 60 Hz | 60 Hz | 60 Hz |
| Engine/Alternator RPM | 3600/3600 | 2300/1800 | 3000/1800 | 3600/3600 |
| Engine | 5.4L V-8 | 6.8L V-10 | 6.8L V-10 | 6.8L V-10 |
| Fuel Consumption LP (cu.ft./hr.)/(gal./hr.) |
554 (15.02) | 507 (13.9) | 719 (19.8) | 830 (22.8) |
| Fuel Consumption NG (cu.ft./hr.) | 1374 | 1260 | 1786 | 2061 |
| EPA/CARB Certified | Yes | Yes | Yes | Yes |
| Fuel | Natural Gas LP Vapor |
Natural Gas LP Vapor |
Natural Gas LP Vapor |
Natural Gas LP Vapor |
| Engine Cooling | Liquid | Liquid | Liquid | Liquid |
| Controls | H-100 | H-100 | H-100 | H-100 |
| UL 2200 (US and Canada) | Yes | Yes | Yes | Yes |
| Sound Output dB(A) at 23 ft. with generator operating at full load | 75 | 74 | 74 | 76 |
| Sound Output dB(A) at 23 ft. with generator in WhisperTest™ low speed exercise mode | 62 | 61 | 61 | 62 |
| Main Line Circuit Breaker | 450, 400, 175 Amp | 450, 400, 175 Amp | 600, 500, 225 Amp | 700, 600, 250 Amp |
| Aluminum Enclosure Option | Yes | Yes | Yes | Yes |
| Dimensions (L" x W" x H") | 115.2 x 36.8 x 54.8* | 115.2 x 36.8 x 54.8* | 115.2 x 36.8 x 54.8* | 115.2 x 36.8 x 54.8* |
| Unit Wt. (lbs.) (steel/aluminum) | 2311/2137 | 2705/2531 | 2873/2699 | 2666/2492 |
* Does not include measurement of exhaust stack(s)
Controls and Transfer Switch
|
|
|
| 7 LED Indicator Lights | Standard | ||||||||
| High Temperature Shutdown | Standard | ||||||||
| Low Coolant Level Shutdown | Standard | ||||||||
|
|||||||||
| Engine Start Sequence | Cyclic Cranking: Initially 15 sec. on, then 7 sec. rest, 7 sec. on. 90 sec. maximum duration | ||||||||
| Safety Fuse | Standard | ||||||||
| Starter Lockout | Starter cannot re-engage until 5 sec. after engine has stopped | ||||||||
| 2 Amp Battery Charger | Standard | ||||||||
| Engine Warm-up | 10-15 seconds | ||||||||
| Engine Cool-down | 1 minute | ||||||||
|
|||||||||
| Automatic Weekly Exerciser with Selectable Low Speed Exercise | Standard | ||||||||
|
|
|
|
| 32-Bit Microprocessor | Single point of control for engine, generator and transfer switch functions | ||||||||
|
|||||||||
| Sealed Casing | Protects against vibration, dust, heat moisture, corrosion, radio interference, electromagnetic interference and static discharge | ||||||||
| Low Coolant, Hight Temperature and Low Oil Pressure Automatic Shutdown | Standard | ||||||||
| Digital Readout of AC kW, kVA, Power Factor and All Engine Functions | Standard | ||||||||
| Isochronous Govenor Control | Standard | ||||||||
| Predictive Maintenance Reminders | Standard | ||||||||
| 3 Phase Sensing | Protects motor by monitoring voltage across all 3 phases | ||||||||
| 2 Amp Automatic Battery Charger | Standard | ||||||||
| Fault Protection (I2T Function) | Provides total generator winding protection under all fault conditions | ||||||||
| Start/Stop Control | Programmable auto-crank feature | ||||||||
| Starter Lockout | Standard | ||||||||
| Automatic Weekly Exerciser with Selectable Low Speed Exercise | Standard | ||||||||
| Overspeed/Over-voltate Protection | Standard | ||||||||
| Overcrank Protection | Standard | ||||||||
| Emergency Stop | Standard | ||||||||
| RS485 Remote 2-way Communication with HTS Transfer Switch | Standard | ||||||||
| RS232 & RS485 Outputs | Computer connections for remote monitoring and remote adjustments (with optional model and GenLink software) | ||||||||
|
|
|
|
| Liquid-cooled models with 3.0 liter engines or smaller use RTS transfer switches (100-400 amps). |
| Liquid-cooled models with engines over 3.0 liters use HTS transfer switches (100-800 amps). |
| For more information please see the Transfer Switch page. |
Features
and Benefits
Automotive Engine
GUARDIAN Elite™ generators use modified automotive engines that can easily
be serviced using readily available, cost-effective parts. These engines are
produced in high volume allowing to pass along the cost savings to our
customers.
Whisper-Test™
Reduces noise to a whisper by lowering engine speed during the
generator’s weekly self-test. The Whisper-Test sound level is comparable to
a car at idle and is 50% quieter than the competition.
Superior Paint
New textured, powder coat paint process provides consistent coverage
and better bonding to seams and exposed edges. This ensures greater durability
and a longer lasting finish.
Aluminum Enclosure
GUARDIAN Elite generators are available in a corrosion-resistant
aluminum enclosure to better withstand the elements. This option is especially
important for businesses in southern and coastal communities.
Automatic Exerciser
An automatic seven (7) day test of your system allows you to verify
that your generator is in peak operating condition at all times.
Automatic Transfer Switch
The automatic transfer switch automatiy switches the source of
power from utility to the generator within seconds of a power outage. Because
it’s automatic, you never have to flip a switch.
Convenient Fuel Supply
GUARDIAN Elite generators operate on natural gas or LP gas service.
This provides you with unlimited run time during extended utility power
failures.
Maintenance Friendly
GUARDIAN Elite generators feature large, removable doors. This provides
easy and quick access for servicing and maintenance.
Automatic Safety Shutdowns
Automatic safety shutdowns protect the engine and generator in the
event of low oil pressure, high temperature, overspeed and/or overcrank.
Protective Enclosure
The enclosure protects your generator from harmful weather and includes
key locks for security. Sound-absorbing panels also reduce exterior noise
levels.
Battery Charger
A built-in battery charger ensures that the battery remains at an
optimum performance level.
UL-Listed
For your safety, GUARDIAN standby generators are UL 2200 listed and all
transfer switches are UL 1008 listed. This validates safety and kilowatt
ratings.
EPA and CARB Emission Requirements
Generators up to 25kW must comply with EPA and CARB emissions
requirements. All GUARDIAN generators up to 25 kW meet these requirements.
Made in USA ![]()
Manufactured by Generac Power Systems, we design and build our complete
product from the controls to the enclosures. This ensures that all GUARDIAN
Elite products are built to our highest standards.
|
GUARDIAN Elite™ Spec Sheets
|
|
Shipping cost may be extra - for shipping quote and ship time *Cash discount for wire transfer
* Cash discount for wire transfer
** Delivery time may be up to 8 weeks during natural disasters. Plan ahead
for Hurricane Season!!
Transfer Switches | Generator Control Panel | Home
Commercial single phase and commercial three (3) Phase Rated Amps at 120/208V,
0.8pf Generac Guardian Elite Models
Copyright 2005 Best
Generators | Legal Notices
Copyright 2006 Power Generators